Insulation Resistance Testing on 275 kV Circuit Breakers at GITET Arun Based on PT PLN (Persero) Directive SKDIR 520

Authors

  • Azzumar Universitas Pembangunan Panca Budi
  • Rahmaniar Universitas Pembangunan Panca Budi
  • Siti Anisah Universitas Pembangunan Panca Budi

Keywords:

Isolation resistance, Circuit Breiakeir, maintenance, SKDIiR 520 PT PLN (Persero)

Abstract

The insulation resistance test on the 275 kV Circuit Breaker (CB) at GITET Arun is a crucial step in maintaining the electrical system’s reliability and safety. This study aims to analyze the insulation resistance test results before and after maintenance, based on the SKDIR 520 PT PLN (Persero) standard. The method involves measuring insulation resistance using an Insulation Resistance Tester (Megger MIT 525) and evaluating the effectiveness of maintenance activities such as cleaning bushings and stubs. The test results indicate that after maintenance, the insulation resistance values increased by an average of 30% at the upper terminal, lower terminal, and upperlower terminal, thereby meeting the established operational standards. In conclusion, routine maintenance improves CB insulation resistance values and ensures the reliability of the power system

References

Hasibuan, A. (2017). Analisis Stabilitas Sistem Tenaga Listrik Single Mesin Menggunakan Metode Runge Kutta Orde 4. Jurnal Elektro Dan Telkomunikasi, Vol 4(No. 2), 24.

Rahmaniar, Pristisal Wibowo, P. M. (2022). Transient Stability Analysis With Critical Clearing Time Method On Transmission Line 150 KV. [1] P. M. Rahmaniar, Pristisal Wibowo, “Transient Stability Analysis With Critical Clearing Time Method On Transmission Line 150 KV,” 2022. https://jurnal.pancabudi.ac.id/index.php/keputeraan/article/view/4296/3904

Malik, T. Al, Tharo, Z., Gunawan, H., Pura, P. T., Binjai, B. P., & Penghantar, B. (2025). Analisis Pengujian Pemutus Tenaga ( PMT ) 150 KV Bay Penghantar Tanjung Pura di Gardu Induk Pangkalan Brandan untuk menyalurkan energi listrik secara terus – menerus kepada setiap pelanggannya [ 1 ]. Di terga nggunya sistem proteksi pada gardu induk . Oleh karena itu , diharuskan adanya perawatan pemeliharaan pada sistem penyaluran transmisi . Pemeliharaan yang dilakukan adalah Pemeliharaan Pemutus Tenaga ( PMT ) 150 kV Bay Penghantar Tanjung Pura di Gardu Induk Pangkalan Brandan ”. Gardu Induk Pangkalan Brandan terletak di Kabupaten Langkat , Sumatera Utara . Pada 60 MVA tegangan kerja 150 / 20 kV dan memiliki 4 Bay Penghantar 150 kV yaitu Bay. 5, 851–863.

Khoirunnisa, N., & Cahyono, B. D. (2025). PREVENTIF PEMELIHARAAN CIRCUIT BREAKER 150 kV DI GARDU INDUK CILEGON BARU BAY PLTGU 1. Teknika, 10(1), 53–61. https://doi.org/10.52561/teknika.v10i1.430

Satpathy, R., & Pamuru, V. (2021). Chapter 10 - Grid integration, performance, and maintenance of solar PV power systems. In R. Satpathy & V. Pamuru (Eds.), Solar PV Power (pp. 435–481). Academic Press. https://doi.org/https://doi.org/10.1016/B978-0-12- 817626-9.00010-1

Aribowo, D., Permata, E., Desmira, Ekawati, R., Hamid, M. A., Fakthurrohman, M., Dharmawan, M. I., Irwanto, & Bahtiar, K. (2018). AnalisisHasilUji PMT150kV PadaGarduInduk CilegonBaruBAY KS 1. Jurnal Teknik Elektro Dan Vokasional, 5(1), 59–65.

Susanto, A., Kurnianto, R., & Rajagukguk, M. (2021). Analisa Kelayakan Pemutus Tenaga (Pmt) 150 Kv Berdasarkan Hasil Uji Tahanan Isolasi, Tahanan Kontak Dan Keserempakan Kontak Di Gardu Induk Singkawang. Fakultas Teknik Universitas Tanjungpura, 1–9.

HARMATA, G. (2020). Analisa Perbandingan Hasil Pengujian Circuit Breaker Menggunakan Breaker Analyzer Dan Tan Delta. 57.

Sianipar, T. P., Wibowo, P., & Tharo, Z. (2025). An Analysis of Performance Comparison of Circuit Breaker Protection Systems in Packing and Picking Operations at PT. Shippindo Teknologi Logistik. Journal of Computer Science, Information Technology and elecommunication Engineering, 6(1), 824–834. https://doi.org/10.30596/jcositte.v6i1.23676

Prakoso, M. A., Elektro, S. T., Teknik, F., Surabaya, U. N., Elektro, S. T., Teknik, F., Surabaya, U. N., Kunci, K., Tenaga, P., Isolasi, T., Kontak, T., & Kontak, K. (2024). Analisis Pengujian dan Pemeliharaan Dua Tahunan Pemutus Tenaga ( PMT ) Di Gardu Induk Rungkut 150 kV Joko, Achmad Imam Agung, Fendi Achmad Abstrak Pemeliharaan instalasi tenaga listrik di Gardu Induk melibatkan serangkaian pengujian untuk memastikan kea. Analisis Pengujian Dan Pemeliharaan Dua Tahunan Pemutus Tenaga (PMT) Di Gardu Induk Rungkut 150 KV, 13, 144–151.

Akbar, N. Z. (2025). Pengkoreksian dan maintenance nilai tahanan isolasi stator pada motor induksi 3 phasa tugas akhir. Universitas Sultan Syarif Kasim Riau.

Djodding, I. M. (2024). Analisis Pengujian Shutdown Measurement Transformator Arus 150 Kv Pada Gardu Induk Tello. Universitas Muhammadiyah Makassar

Yusniati, Pelawi, Z., Armansyah, & Taufik Imam. (2021). Pengukuran Resistansi Isolasi Instalasi Penerangan Basement Pada Gedung Rumah Sakit Grend Mitra Medika Medan. Buletin Utama Teknik, 16(3), 240–247.

Lubna Nadra Hasti, & Irwanto Irwanto. (2023). Maintenance Circuit Breaker SF6 kV Unit 3-4 di PT.Indonesia Power Suralaya. Jurnal Teknik Mesin, Industri, Elektro Dan Informatika, 2(1), 205–216. https://doi.org/10.55606/jtmei.v2i1.1395

SKDIiR 520 PT PLN Peidoman Peimeiliiharaan Peiralatan Peinyaluran Teinaga

Hutajulu, A., Malino, M., & Tambunan, J. (2024). Implementasi Pengujian Karakteristik Miniatur Circuit Breaker Berdasarkan Sni 60898-1:2009 Di Pt Pln (Persero) Pusat Sertifikasi. Prosiding Seminar Nasional Penelitian LPPM UMJ, 1–10. http://jurnal.umj.ac.id/index.php/semnaslit

Galih Firdaus, A., & Hidayat, R. (2021). Analisa Pengujian Kelayakan Operasi Pemutus Tenaga (PMT) 150 kV Bay Penghantar Mandirancan I Berdasarkan Parameter Breaker Analyzer di Gardu Induk Sunyaragi. Electrician, 15(3), 252–267. https://doi.org/10.23960/elc.v15n3.2195

Review dan Revisi KEPDIR No. 0520 K/DIR/2014 Pedoman Pemeliharaan Peralatan Penyaluran Tenaga Listrik PT PLN (Persero)

Makkulau Andi, Nurmiati, dkk, 2018. Pengujian Tahanan Isolasi dan Rasio pada Trafo PS T15 PT INDONEiSIiA POWER UP MRICA. Sekolah Tinggi Teiknik – PLN

Ramansyah Dikky, Friska, dkk, 2023. Analisis Pengujian Tahanan Isolasi Stator dan Rotor Generator GT 1.1 PLTG Belawan. Politeknik Negeri Medan, Medan.

Downloads

Published

2025-10-27