Analysis of Power Losses in 6.3 Kv Step Down Transformers at PT. Permata Group

Authors

  • Daendi Sihombing Universitas Pembangunan Panca Budi
  • Parlin Siagian Universitas Pembangunan Panca Budi
  • Muhammad Ervandi Dalimunte Universitas Pembangunan Panca Budi

Keywords:

Step-Down Transformer, Power Loss, Efficiency, Loading Factor, Load Optimization, Under-Utilization

Abstract

This study analyzes power losses in a 6.3 kV step-down transformer with a capacity of 4,000 kVA at PT Permata Group, which distributes energy from the medium voltage system to the low voltage system. The analysis is based on nameplate data and field measurements, covering core losses (P₀), copper losses (Pcu), efficiency, and the effect of harmonics. The results show an increase in copper losses from 32,000 W to 32,080 W and core losses from 4,500 W to 5,200 W. The THD current value of 5.0% is still in accordance with the IEEE 519-2014 standard (≤8%). Maximum efficiency was achieved at 80% load with an actual value of 99.13%, slightly lower than the nameplate value of 99.17%. The transformer's condition was found to be very good and can serve as a reference for predictive maintenance and industrial power quality evaluation.

References

Anisah, S., Wardani, D. P., Rahmaniar, R., & Hamdani, H. (2020). ANALYSIS OF OVER CURRENT RELAY (OCR) ON 60 MVA POWER TRANSFORMERS WITH MATLAB SIMULATION AT THE PAYA GELI SUBSTATION. In Scenario (Seminar of Social Sciences Engineering and Humanities) (pp. 262-270).

Roza, I., Nasution, A. A., & Setiawan, H. (2019). Analysis of oil age on the temperature of 150kV transformers due to a decrease in breakdown voltage at the 2.1 pt pln (persero) Belawan power generation unit gas-fired power plant (PLTG). Journal of Electrical and System Control Engineering, 3(1), 1-12.

Fajri, S., Wibowo, P., & Hamdani, H. (2025). Analysis of transformer turn ratio test results on 60 MVA power transformer at Simpang Tiga substation PT. PLN (Persero) Ultg Prabumulih. Fidelity: Journal of Electrical Engineering, 7(1), 1-10.

Adami, R., Irianto, C., Sari, T., & Kasim, I. (2024). Analysis of the effect of load on the efficiency and age reduction of 630kva dry transformers in the Jakarta Integrated Mass Rapid Transit System. Transmission Journal of Electrical Engineering, 26(4), 185-191. https://doi.org/10.14710/transmisi.26.4.185-191

Adami, R., Irianto, C., Sari, T., & Kasim, I. (2024). Analysis of the effect of load on the efficiency and age reduction of 630kva dry transformers in the Jakarta integrated mass transit system. Transmisi Jurnal Ilmiah Teknik Elektro, 26(4), 185-191. https://doi.org/10.14710/transmisi.26.4.185-191

Amrollahi, M., & Hassani, S. (2024). Determination of losses and estimation of the life of distribution transformers using three computational, measurement, and simulation methods, despite harmonic loads. Renewable Energy and Power Quality Journal, 9(1). https://doi.org/10.24084/repqj09.511

Ananda, T., & Gusnita, N. (2023). Comparative analysis of the effect of stator and rotor iron core materials on efficiency in an 18-slot 18-pole permanent magnet synchronous generator. Al-Azhar Indonesia Journal of Science and Technology, 8(2), 105. https://doi.org/10.36722/sst.v8i2.1833

Ardiansyah, M., & Hidayat, R. (2022). Analysis of the Bucholz mechanical protection system on a 150kv/20kv transformer at PT PLN (Persero) UPT Bekasi. Aisyah Journal of Informatics and Electrical Engineering (AJIEE), 4(2), 116-121. https://doi.org/10.30604/jti.v4i2.119

Arif, H., & Wahyono, E. (2022). The effect of peak load on power transformer efficiency. JST.UNSADA, 12(2), 34-40. https://doi.org/10.70746/jstunsada.v12i2.247

Bhuana, C., Tasrif, T., Djalal, M., Andini, N., & Rezaldy, M. (2022). Designing a micro-hydro power plant prototype using a Pelton turbine. Jurnal Teknik Mesin Sinergi, 20(1), 110-114. https://doi.org/10.31963/sinergi.v20i1.3482

Bhuana, C., Tasrif, T., Djalal, M., Andini, N., & Rezaldy, M. (2022). Design and construction of a micro-hydro power plant prototype using a Pelton turbine. Journal of Mechanical Engineering Synergy, 20(1), 110-114. https://doi.org/10.31963/sinergi.v20i1.3482

Fayumi, F., Putra, D., & Aryani, N. (2022). Dynamic reconfiguration of the 20 kV Teluk Betung radial distribution network to improve voltage profiles by considering line disturbances and renewable energy injection. ITS Engineering Journal, 11(2). https://doi.org/10.12962/j23373539.v11i2.92298

Febrianingrum, A., & Pramono, S. (2022). SAIFI for evaluating the reliability of the electrical power distribution system in a 20 kV medium-voltage transmission network. Journal of Electrical Engineering Technology, 21(1), 1. https://doi.org/10.24843/mite.2022.v21i01.p01

Guo, L., Cai, F., Zhu, Q., Yuan, S., Wang, D., & Zhou, L. (2022). A fast calculation method of transient hot spot temperature for the design of dry-type on-board transformers. IET Electric Power Applications, 17(1), 68-79. https://doi.org/10.1049/elp2.12246

Huwae et al. (2025) P. T. (2022). "The Effect of Load Factors on Transformer Efficiency in Distribution Systems." Journal of Renewable Energy, 15(3), 194-201

Huwae, J., Haurissa, M., & Latupeirissa, H. (2025). Analysis of the effect of loading on the efficiency of a 30 MVA power transformer at the Ambon Peaker 30 MW PLTMG. Fortech Journal, 6(1), 1-8. https://doi.org/10.56795/fortech.v6i1.6101

Mulyadi et al. (2023). Mardiana, A., & Hasan, I. (2023). "Analysis of Power Loss in Transformers in Distribution Networks." Journal of Electrical Engineering, 11(2), 78-85

Downloads

Published

2025-10-27